TROUBLESHOOTINGSPLIT AIR CONDITIONERWITH HEAT PUMPSOPHIA

Page 2

1.3.2 Indoor / outdoor unit’s communication diagnosis and solution(E1) Error Code E1 Malfunction decision conditions Indoor unit does not receive the

Page 3

Remark: Use a multimeter to test the DC voltage between 2 port and 3 port of outdoor unit. The red pin of multimeter connects with 2 port while t

Page 4 - 3W- 10m1%

1.3.3 Zero crossing detection error diagnosis and solution (E2) Error Code E2 Malfunction decision conditions When PCB does not receive zero crossing

Page 5 - 4 - WA Y

1.3.4 Fan speed has been out of control diagnosis and solution(E3) Error Code E3/F5 Malfunction decision conditions When indoor fan speed keeps too lo

Page 6

Index 1: 1:Indoor or Outdoor DC Fan Motor(control chip is in fan motor) Power on and when the unit is in standby, measure the voltage of pin1-pin3, p

Page 7 - HI GHL OW

1.3.5 Open circuit or short circuit of temperature sensor diagnosis and solution(E5) Error Code E4/E5/F1/F2/F3 Malfunction decision conditions If the

Page 8 - I C1 424C08

1.3.6 Refrigerant Leakage Detection diagnosis and solution(EC) Error Code EC Malfunction decision conditions Define the evaporator coil temp.T2 of th

Page 9 - 1.3 Diagnosis and Solution

1.3.6 Overload current protection diagnosis and solution(F0) Error Code F0 Malfunction decision conditions An abnormal current rise is detected by che

Page 10

1.3.7 IPM malfunction or IGBT over-strong current protection diagnosis and solution(P0) Error Code P0 Malfunction decision conditions When the voltag

Page 11

For example: P-U P-V Note: The photos below are only for reference, it’s may be not same totally with the ones on your side.

Page 12 - Check if the connections and

1.1 Indoor Unit Error Display Operation lamp Timer lamp Display LED STATUS ☆ 1 time X E0 Indoor unit EEPROM parameter error ☆ 2 times X E1 Indoo

Page 14

N-V N-W

Page 15 - E4/E5/F1/F2/F3

For 30K~36K: At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or close to 0, the IPM is def

Page 17 - Compressor checking]. Is it

1.3.8 Over voltage or too low voltage protection diagnosis and solution(P1) Error Code P1 Malfunction decision conditions An abnormal voltage rise or

Page 18 - ● Outdoor PCB faulty

1.3.9 High temperature protection of IPM module or compressor top diagnosis and solution(P2) Error Code P2 Malfunction decision conditions If the samp

Page 19 - For example:

1.3.10 Inverter compressor drive error diagnosis and solution(P4) Error Code P4 Malfunction decision conditions An abnormal inverter compressor drive

Page 20

Digital tester Normal resistance value Digital tester Normal resistance value (+)Red (-)Black ∞ (Several MΩ) (+)Red (-)Black ∞ (Several MΩ) P N U N U

Page 21

1.3.11 Low pressure protection diagnosis and solution(P6) Error Code P6 Malfunction decision conditions When the pressure of system reach a certai

Page 22

Main parts check 1. Temperature sensor checking Disconnect the temperature sensor from PCB, measure the resistance value with a tester. Temperature

Page 23

1.2 Outdoor unit error display(TBD) For CH-09SPH-115VO, CH-12SPH-115VO, CH-09SPH-230VO, CH-12SPH-230VO, N11712200001919511[ 1. 6] 2015- 09- 30US- K

Page 24 - ● System leakage or block

Appendix 1 Temperature Sensor Resistance Value Table for T1,T2,T3,T4 (°C--K) °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm -20 -4 115.266 20 68

Page 25 - Measure the resistance

Appendix 2 Temperature Sensor Resistance Value Table for TP (°C --K) °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm -20 -4 542.7 20 68 68.66

Page 26

Appendix 3: ΔT(℉) =9ΔT(℃)5 °C °F °C °F °C °F °C °F °C °F -5 23 21 69.8 51 123.8 82 179.6 113 235.4 -4 24.8 22 71.6 52 125.6 83 181.4 114 237.

Page 27

Appendix 4 1. Normal voltage of P and N 208-240V(1-phase,3-phase) 380-420V(3-phase) In standby around 310VDC around 530VDC In operation With passiv

Page 28 - ● PCB faulty

2. Compressor checking Measure the resistance value of each winding by using the tester. Position Resistance Value ASN98D22UFZ ASM135D23UFZ ATF235

Page 29

3. Fan Motor Measure the resistance value of each winding by using the tester. Model YKT-32-6-202L YKT-32-6-3L YKT-48-6-206 YKT-63-6-200L Brand

Page 30

4. Pressure On Service Port Cooling chart: °F(°C) ODT IDT 75 (23.89) 85 (29.44) 95 (35) 105 (40.56) 115 (46.11) BAR 70/59 8.2 7.8 8.1 8.6

Page 31

Heating Chart: °F (°C) ODT IDT 57/53 (13.89/11.67) 47/43 (8.33/6.11) 37/33 (2.78/0.56) 27/23 (-2.78/-5) 17/13 (-8.33/-10.56) BAR 55 30.3 28.5

Page 32

1 Front panel How to remove the front panel. 1) Pull the below side of the panel toward you and remove screw of the cover. 2) Release the connector

Page 33

2 Electrical parts How to remove the electrical parts. 1) Remove the front panel from procedure 1. 2) Pull out the room temp. sensor (T1). Remove

Page 34

For CH-09SPH-230VO, CH-12SPH-230VO, CH-18SPH-230VO, CH-18SPH-230VO +T4TPT3NLHNNRd iHa v eLow-FreYESNONoUBL UEVREDWBLACKTESTPORTP MVDC- F ANDR_ LDR

Page 35 - 3. Fan Motor

For CH-24SPH-230VO, Suct i onExhaust+17122200000309Hu i QiTe s t Po r t11HEAT4 - WA YWBL UEBLACKREDVUTPT3T4NoNONOYESLow- Fr

Page 36 - Cooling chart:

After power on, LED3(Green color) and LED2(Red color) will be flash if the unit has some problems. No. Problems LED3 (Green) LED2 (Red) IU display 1

Page 37 - 2.1 Indoor unit

For CH-S30FTXW-SV, CH-S36FTXW-SV, NLSHOW/ SWEARTH[ 1. 4] 2014. 06. 26EU- KFR105W/ BP3T5N1- 350S. D. 13. WP1- 1L - OUTN- OUTCONNECT TO INVERTER driver

Page 38 - ①1 screw

IPM board, 202302141237PF C- L2[ 1. 6] 20 14 . 10. 16EU- KFR105W/ BP2T3N1- 350( 767) . D. 13. MP2- 1PF C- L1EARTH+CN55T O- MA I NWVUI P M2I P M1I C1

Page 39

1.3 Diagnosis and Solution 1.3.1 EEPROM parameter error diagnosis and solution(E0/F4) Error Code E0/F4 Malfunction decision conditions Indoor or outd